The VVP10 is a smart positioner designed to work with linear or rotary valve actuators, providing precision and control with high availability and reliability. It allows easy installation and commissioning and it is suitable for various types of valves, regardless of type and size.
VVP10 positioners are available in HART® 7 / 4-20mA and PROFIBUS PA technologies. HART® model has in its standard model the feedback signal (4-20mA) to indicate the current controlled position.
VVP10 also offers a model with pressure sensor, digital inputs (limit switches), outputs (for alarms and safety solenoid valves) and advanced diagnostics that help to predict efficiently the need for maintenance.
The DTM Libraries for HART and Profibus-PA devices can be found on:
HART Profibus-PA
Performance | Linearity: < ±0.1% Full Scale (using user table) Resolution: < 0.1% Full Scale Repetibility:< 0.1% Full Scale Hysteresis: < 0.1% Full Scale |
Air Supply Effect | Negligible |
Position Sensor | Sensor without contact, Hall effect, Local or Remote |
Power Supply for Device | 4-20 mA, no polarity |
Power Supply for Position Feedback | 12-45 Vdc (open collector), Isolation 1500 Vdc (Feedback 4-20 mA @12 bits, 4 uA resolution, 0.1% accuracy) |
Communication Protocol / Configuration | HART 7 Remote configuration using EDDL or FDT/DTM tools. Local configuration using magnetic tool. |
Classified Area Certification | Intrinsically Safe and Explosion Proof |
Air Supply Pressure / Output Pressure Range | 1.4 – 9.65 bar (20 -140 psi). Oil, dust and water free, according to ANSI/ISA S7.0.01-1996 standard. / 0 to 100% of Air Supply Input |
Air Consumption | 40 psi (2.8 bar): 6 l/min (0.21 cfm) 80 psi (5.5 bar): 9,5 l/min (0.34 cfm) |
Flow Capacity | 116 psi (8 bar): 283 l/min (10 cfm); |
Setpoint Characterization | Linear, Equal Percentage, Quick Open and User Table (up to 16 points) |
Environment Temperature Limits | Ambient: -40 to 85 °C (-40 to 185 °F) Storage: -40 to 90 °C (-40 to 194 °F) LCD: -10 to 80 °C (14 to 176 °F) operation. -40 to 85 °C (-40 to 185 °F) no damage. Remote Sensor Operation: -40 to 105 °C (-40 to 221 °F) |
Humidity Limits | 0 to 100% RH (Not-Condensable Relative Humidity) |
Vibration Effects | ± 0.3%/g of span during the following conditions: 5-15 Hz for 4 mm constant movement. 15-150 Hz for 2g. 150-2000 Hz para 1g. Follows IEC60770-1. |
Electromagnetic Interference Effects | According to IEC 61326:2002 |
LCD Display | 5-digit, rotative, multi-function and bargraph |
Stroke Movement | Linear: 3 to 100 mm Rotative: 30 to 120° |
Action Type | Direct and Reverse, Single and Double, Air to Open or Air to Close |
Self-Calibrations and Advanced Diagnostics | Position Self-Calibration and PID Self-Tuning FST (Valve Signature) and PST Diagnosis (with pressure sensors) |
Mounting | Using universal brackets for linear and rotative actuators/valves |
Pressure Sensors - Optional | For input, output 1 and output 2 pressure measurement. |
Discrete Inputs (Stroke-Limits) - Optional | 2 isolated dry contact inputs |
Discrete Outputs (Safety Valves/Solenoid) - Optional | 2 open-collector outputs, max. 400 mA, 24 Vdc |
Electrical Connection | 1/2 - 14 NPT |
Pneumatic Connection | Input and Outputs: 1/4 -18 NPT. Pressure Gauges: 1/8 - 27 NPT |
Housing Material | Aluminum / Plastic (only pneumatic block lid) |
Approximated Weight | 3 kg (without mounting bracket) |
Pressure Gauges - Optional | Input and output pressures monitoring. 0-160psi scale. ABS housing, polycarbonate display, brass connection. |
Main Benefits:
• HART® 7 / 4-20mA and PROFIBUS-PA
• Compact, high-performance, multifunctional
• Designed to operate under severe conditions and high robustness with instrumentation air
quality
• Electronic coil technology
• Non-contact position sensor (Hall sensor)
• Suitable for most brands of valves / actuators
• Single and double actions
• Remote position sensor available for high vibration and high temperature applications
• Auto-Setup, Auto-Tuning, Partial Stroke Test, Position Histogram and Advanced
Diagnostics
• Usual or user-defined characterization curves (table)
• Pressure sensors
• Air supply pressure from 20 to 140 psi
• Actuator stroke
- Linear 3 to 100 mm and rotary 30 to 120 °
• 5-digit rotary, alphanumeric and bar graph LCD
• Local Adjustment
• Supports DD, EDDL and FDT / DTM
• 02 Digital inputs (limit switch) and 02 Digital outputs (for solenoid safety valve actuation)
• Standard model HART 7 4-20mA: with feedback position signal (4-20mA)