VIO10 is a remote I/O with Profibus-PA communication, designed for field or panel (with DIN rail) installation.
It has great versatility with temperature inputs, 4-20 mA inputs and outputs, digital inputs and outputs on a single hardware.
The DTM Library for Profibus-PA devices can be found on:
Profibus-PA
Accuracy | Temperature: According to Tables Above Inputs / Outputs: ± 0.1% Span calibrated |
Supply Voltage / Quiescent Current Output Load Limit | 9 to 32 Vcc, no polarity / 12 mA |
Protocol of Communication / Function Block | Profibus-PA / 16 Discrete Input (DI) 08 Discrete Output (DO) 03 Analog Input (AI) 02 Analog Output (AO) |
Certification in Hazardous Area | Intrinsically Safe (pending) |
Ambient Temperature Limit | -20 to 70°C |
Configuration | Remote configuration through tools based on EDDL or FDT / DTM. Local configuration via magnetic key. |
Mounting | In field or panel, using DIN rail |
Degree of Protection | IP20 |
Type of Electrical Insulation (between Profibus-PA bus, inputs and outputs) | Galvanic Isolation, 1,5 kVac |
Housing Material | Aluminum / Plastic |
Approximate weight | 500 g |
Discrete Inputs | 16 Inputs Typical external power supply: 24 Vdc (18 to 30 Vdc, maximum consumption 120mA) Optical Isolation of 5,000 Vac. Level in ON state (True Logical) 15 - 30 Vdc. Level in OFF state (Logical False) 0 - 5 Vdc Typical Impedance 3.9 kW. |
Discrete Outputs | 8 Outputs: NPN transistors, open collector. They work with relays, solenoids and other DC loads with maximum current of 0.5 A per output. All outputs share the same ground and are isolated from each other, as well as from the Profibus-PA network. Typical external power supply 24 Vdc (18 to 30 Vdc, max. 40mA) - same source of inputs, 24Vdc Optical Isolation of 5,000 Vac Maximum switching voltage: 30 Vdc Maximum Saturation Voltage: 0.55 V at 0.5 A Maximum Output Current: 0.6 A Indication logic: ON when the transistor is on. Power-Up Condition: OFF Thermal Protection: Thermal Shutdown: 150-200 ° C; Thermal Hysteresis 10 at 25 ° C; Over current protection: 1.3 A at 24 Vdc maximum * With inductive loads use RC filters or diode in reverse mode as filter. |
Main benefits:
• A single node in the Profibus-PA network with consumption of 12mA
• Reduced installation and design cost through the availability of 16 digital inputs, 8 digital outputs, 3 temperature channels and analog input and output signal converters
• Easily enables the integration of output devices (eg valve positioners) and HART / 4-20 mA input (transmitters) in Profibus-PA networks
• Easy configuration of inputs and outputs
• Several measurement and sensor types (T/C, RTD, mV and ohm)
• Self-diagnosis
• 5 digit rotary, multifunctional and bargraph LCD
• Local adjustment intuitive, configurable and with fast editing function