VBP10 is a bus protector for Profibus-PA and FOUNDATION ™ fieldbus networks according to IEC 61158-2, which ensures that a short circuit generated in their spurs not propagate to other spurs and to the main trunk. In short circuit condition (between + and - signs + or shield) the spur opens, preventing the short circuit. For each spur there is a LED which is activated in the short circuit condition. From time to time, VBP10 checks for current flowing in the spur, and if there is current, it is activated again. After leaving the short-circuit condition, the spur back to work and the protection circuit is disabled, erasing the LED.
Some segment protectors act as short circuit limiters, limiting the current in the range of 40 to 60mA per spur and in a short circuit situation, this current, depending on how the segment is sized, can shut it down (even more if more than one spur is in short circuir) due to excessive consumption and, consequently, to voltage drop.
The VBP10 uses the “FoldBack” technique, where in any situation that the spur consumes more than 48mA, it automatically shuts off the spur until the situation returns to normal. For this, it consumes less than 2mA per spur, which is an advantage over market segment protectors that maintain a permanent fault current, overloading the segment in case of multiple spurs short.
In addition, the VBP10 acts quickly, limiting the inrush current: when the Profibus-PA or Foudantion fieldbus device is powered, a large current flows and exceeds the current steady-state value. This current is called the inrush current. With the use segment protectors with low quality terminal blocks and in vibrating environments, some devices (due to poor contact on these terminal blocks or junction boxes) will turn off and on (contact peaks) and depending on the quality of the protection of this segment, the insrush current may be higher than the current supplied to the segment and "shut down" the bus or dramatically affect communication.
VBP10 has a LED to indicate that the module is powered and also an integrated bus terminator (BT).
The Trunk Input has surge protector, ensuring greater safety to VBP10 and spurs.
In normal operation, i.e. without short-circuit, each spur consumes less than 1 mA. Each spur has a maximum current of 40 mA.
Increase the availability and operational safety of your Profibus-PA or FOUNDATION ™ fieldbus network.
Physical Medium / Protocol | According to IEC 61158-2 / Profibus-PA /FOUNDATION™ fieldbus |
Number of Spurs | 4 and 8 |
Supply Voltage / Current Quiescent per Spur | 9 to 32 Vdc / < 1.0 mA |
Maximum Trunk current | 4.0 A |
Maximum Spur current | 40.0 mA |
Average Spur Current @ Short Circuit condition | 12.0 mA |
Maximum voltage drop per Spur | 0.3V@20mA |
Surge protector at the Trunk Input | 1500 W, cut off level 62 V |
LEDs indicators | Green LED: On – Module powered; Off: Module not powered Red LED: On – Spur protection is activated ; Off: Spur protection is deactivated |
Spurs connections | Removable 3-pin terminal blocks, 2.5 mm² |
Hazardous Certification | Intrinsically Safe (pending) |
Ambient Temperature Limits and Storage | -40°C to 85°C |
Relative humidity | 0-95% non-condensing |
Mounting | DIN rail or junction box |
Dimensions (mm) / Weight (g) | VBP10-4: 125 x 90 x 56 (C x L x A) / 200 g – no Protection Housing VBP10-8: 125 x 142 x 56 (C x L x A) / 400 g – no Protection Housing VBP10-4: 245 x 180 x 168 (C x L x A) / 2.6 kg – Protection Housing VBP10-8: 245 x 280 x 168 (C x L x A) / 4.0 kg – Protection Housing< |
Main Benefits: