VTT10-H is a temperature transmitter for head mounting - DIN Form B-compliant that generates 4 – 20 mA current signal (HART® 7 model) or a digital signal (Profibus-PA model), according to the measurement and user configuration.
The DTM Libraries for HART and Profibus-PA devices can be found on:
HART Profibus-PA
Accuracy | ± 0.01% Calibrated Span |
Power Supply / Output Current | 12 to 45 Vdc, no polarity/4-20 mA according to NAMUR-NE43 |
Communication Protocol | HART® 7 and Profibus-PA Certified HART® Modem |
Hazardous Area Certification | Intrinsically Safe (pending) |
Ambient Temperature Limits | - 40 to 85°C |
Configuration | EDDL and FDT/DTM tools, as well as PALM and Android® platform. |
Assembly | Head Mounting according to DIN 43729 Form B |
Protection Degree | IP00 / IP66 (Installed) |
Electrical Isolation | Galvanic 1.5 kVac |
Housing Material | ABS Plastic |
Dimension / Approximate Weight | Ø 45 x 23 mm / 50 g |
Main benefits: